Paramete
No.
Description
r
4
LVRT
During LVRT, the
reactive
SUN2000 needs to
power
generate reactive
compensati
power to support the
on power
power grid. This
factor
parameter is used to
set the reactive power
generated by the
SUN2000.
High
When the power grid
5
voltage
voltage is abnormally
ride-throug
high for a short time,
h
the SUN2000 cannot
disconnect from the
power grid
immediately and has
to work for some time.
This is called HVRT.
Active
Specifies whether to
6
islanding
enable the active
islanding protection
function.
7
Passive
Specifies whether to
islanding
enable the passive
islanding protection
function.
8
Voltage
The standards of
rise
certain countries and
suppressio
regions require that
n
the active power of the
SUN2000 be derated
according to a certain
gradient when the
output voltage exceeds
a certain value.
Issue Draft A (2017-02-15)
Default
Unit
Value
value prevails.
N/A
N/A
The default
value varies
depending on
the grid code.
The displayed
value prevails.
N/A
N/A
The default
value varies
N/A
depending on
the grid code.
The displayed
value prevails.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Value Range
Remarks
[0, 3]
This parameter is
set to 2.5 by
default if the South
African grid code
is selected.
For example, if
you set LVRT
reactive power
compensation
power factor to 2,
the reactive power
generated by the
SUN2000 is 20%
of the rated power
when the AC
voltage drops by
10% during
LVRT.
Disable
N/A
Enable
Disable
N/A
Enable
Disable
This parameter is
displayed only
Enable
after the Japanese
grid code is
selected.
Disable
This parameter is
set to Enable by
Enable
default if the
Italian grid code
CEI0-16 is
selected.