Huawei SmartLogger2000 User Manual page 193

Hide thumbs Also See for SmartLogger2000:
Table of Contents

Advertisement

SmartLogger2000-(10-C, 11-C)
User Manual
Alarm
Alarm
ID
Name
Abnormal
1101
Q-Control
Issue Draft A (2017-02-15)
Alarm
Alarm
Severity
Sub-ID
4
Major
1
2
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cause
Measures
1. Verify that the cables are connected
Under the active
correctly to the DI ports.
power Dry
contact remote
2. Access the active power Dry contact
control mode,
remote control configuration page and
the four DI
check the mapping table of the DI signal
ports read
configuration. Contact the power grid
command
company and verify that the
combinations
combination configurations in the table
not configured.
are complete and meet the requirements
of the company.
1. On ADAM4117, verify that the port
Under the
corresponding to the AI SN in use is
reactive power
connected to a cable properly. If the
AI/DI remote
cable is not connected firmly, is
control mode,
disconnected, or is not connected
the AI port
correctly, reconnect it firmly and
receives
correctly.
currents outside
the
2. Access the reactive power AI/DI
configuration
remote control configuration page and
range.
check that the start and end current
settings of the AI comply with the
requirements of the power grid
company.
3. Access the Extended Port Settings
page and check that the current
configuration of the AI number is
consistent with the current specification
of the ADAM4117.
4. Contact the power grid company and
verify that the command data sent from
the company is correct.
1. Verify that the communications cable is
Under the
connected correctly to the ADAM4117
reactive power
module and SmartLogger. Verify that
AI/DI remote
the RS485 addresses are not duplicate,
control mode,
and that the baud rate is the same as that
the command
of the corresponding SmartLogger port.
data of the AI
port cannot be
2. Verify that the auxiliary power supply of
read due to the
the ADAM4117 module is normal.
ADAM fault,
power
disconnection,
or abnormal
link.