Huawei SmartLogger2000 User Manual page 109

Hide thumbs Also See for SmartLogger2000:
Table of Contents

Advertisement

SmartLogger2000-(10-C, 11-C)
User Manual
No.
Parameter
Description
7
Grid
The standards of
reconnectio
certain countries and
n voltage
regions require that
lower limit
the SUN2000 must
not connect to the
power grid when the
power grid voltage is
lower than the lower
limit.
8
Grid
The standards of
reconnectio
certain countries and
n frequency
regions require that
upper limit
the SUN2000 must
not connect to the
power grid when the
power grid frequency
is higher than the
upper limit.
9
Grid
The standards of
reconnectio
certain countries and
n frequency
regions require that
lower limit
the SUN2000 must
not connect to the
power grid when the
power grid frequency
is lower than the lower
limit.
10
Reactive
Specifies the voltage
power
threshold for
compensati
triggering reactive
on (cosψ-P)
power compensation
trigger
when LVRT occurs.
voltage
Reactive
Specifies the voltage
11
power
threshold for exiting
compensati
reactive power
on (cosψ-P)
compensation when
exit voltage
the SUN2000 recovers
from LVRT.
Issue Draft A (2017-02-15)
Default
Unit
Value
V
Hz
The default
value varies
depending
on the grid
code. The
Hz
displayed
value
prevails.
%
The default
value varies
depending
on the grid
code. The
%
displayed
value
prevails.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Value Range
Remarks
[45%Vn,
95%Vn]
[100%Fn,
112%Fn]
Fn represents the
rated frequency.
[85%Fn,
100%Fn]
[100, 110]
N/A
[90, 100]
N/A
7 WebUI