Huawei SmartLogger2000 User Manual page 131

Hide thumbs Also See for SmartLogger2000:
Table of Contents

Advertisement

SmartLogger2000-(10-C, 11-C)
User Manual
No
Paramet
Function
.
er
12
IMD
Dry contact No.
control
over which the
dry
SmartLogger
contact
controls the IMD
13
PV
Specifies the
module
offset direction of
compensa
the PID module.
tion
voltage
direction
14
Working
Specifies the
mode
working mode of
the PID module.
Maximum
Specifies the
15
system
voltages between
DC-to-gro
the PV side and
und
PE and between
withstand
the AC side and
voltage
PE in normal
mode.
AC-to-gro
Specifies the
16
und
alarm threshold
resistance
for the impedance
alarm
between the AC
threshold
side of the PID
module and the
ground.
Issue Draft A (2017-02-15)
Value
Description
DO1,
PID01: Set appropriate ports based on the cable
DO2, and
connections between the IMD and the SmartLogger.
DO3
SmartPID2000: N/A
PV–
Select PV– positive offset for PV modules of P and
positive
N-PERT types.
offset
NOTE
For the specific PV module type, consult its manufacturer.
PV+
Select PV+ negative offset for PV modules of the N type
negative
except N-PERT.
offset
Normal
In normal mode, the PID module operates automatically
after the PID module, SUN2000, and SmartLogger
communicate with each other properly.
Commissi
In commissioning mode, set Commissioning output
oning
voltage. The PID module delivers voltage based on the
commissioning output voltage.
NOTE
To check whether the PID module functions properly, it is
recommended that Working mode be set to Commissioning
upon first power-on.
500–1500
Specifies the lower thresholds of the maximum voltage
V
ranges between the SUN2000 DC side (including the
SUN2000, PV module, cable, SPD, and switch) and the
ground and between the SUN2000 low-voltage
grid-connection side (including the SUN2000, AC power
cable, SPD, and switch) and the ground in a PV power
system.
The default value is 1000 V. For the 1500 V SUN2000,
the recommended value is 1500 V.
0.2–100
You can set an alarm threshold for the impedance between
the AC grid and PE for the PID module. If the detected
impedance is below the threshold, the PID module will
generate an alarm.
Huawei Proprietary and Confidential