Huawei SmartLogger2000 User Manual page 99

Hide thumbs Also See for SmartLogger2000:
Table of Contents

Advertisement

SmartLogger2000-(10-C, 11-C)
User Manual
No.
Parameter
Description
3
RCD
RCD refers to the
enhancing
residual current of the
SUN2000 to the
ground. To ensure
device security and
personal safety, RCD
should comply with
the standard. If an AC
switch with a residual
current detection
function is installed
outside the SUN2000,
this function should
be enabled to reduce
the residual current
generated during
SUN2000 running,
thereby preventing the
AC switch from
misoperations.
4
Reactive
In some specific
power
application scenarios,
output at
a power grid company
night
requires that the
SUN2000 can
perform reactive
power compensation
at night to ensure that
the power factor of
the local power grid
meets requirements.
5
Strong
If the value of power
adaptabilit
grid short circuit
y
capacity/power plant
installed capacity is
less than 3 and the
power grid impedance
exceeds the upper
threshold, the power
grid quality will be
affected and the
SUN2000 may be
unable to run
properly. Set Strong
adaptability to
Enable.
Issue Draft A (2017-02-15)
Default
Unit
Value
N/A
Disable
N/A
Disable
N/A
Disable
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Value Range
Remarks
Disable
N/A
Enable
Disable
This parameter is
configurable only
Enable
when Isolation is set
to Input
ungrounded (with
a transformer).
Disable
N/A
Enable
7 WebUI