Section 7 I/O Displays
reference the same channel, only the last loop downloaded participates in warmstart
and is listed on the S100 I/O Display.
Operation Action
With warmstart configured for output FCMs and device loops, the authorized user
should:
For continuous loops with Analog and Digital Output FCMs or device loops
configured for warmstart that have been warm started, the tag is shown with a
white background.
When CCF loops with output FCMs configured for warmstart are placed in the
MANUAL mode by either a warmstart or user action, their tags are shown with a
white background. When device loops configured for warmstart have their
DEV_CMND parameter set to NO COMMAND by either a warmstart action or
TCL command, their tags are also shown with a white background. Note that the
loop warm started for a given channel is the loop whose tag is shown in the S100
I/O Display. If two or more loops reference the same channel, only the last loop
downloaded participates in warmstart and is listed on the S100 I/O Display.

PROFIBUS Displays

These PROFIBUS runtime displays relate to a PROFIBUS process interface.
3BUR002418-600 A
Acknowledge device acquisition diagnostics (at node startup, it is assumed all
boards present are warm started).
Call up the corresponding S100 I/O Display to determine which tags are
affected by warmstart.
Make any necessary modifications to synchronize the control system with the
current outputs.
Commission affected CCF output FCMs by setting their modes to AUTO.
Commission affected CCF device loops by issuing device commands (if
desired).
PROFIBUS Displays
167