PID Controller FCM
CHANGE OUTPUT ON FAIL Field
This field specifies if a new output value is supplied upon a remote link failure.
Valid entries are:
LINK TIME-OUT Field
This field specifies the initial time interval for the watchdog timer. The timer is used
to determine whether a supervisory program can continue to control the loop. Valid
entry is a number of seconds
BALANCE MODE Field
This field indicates whether the system can manipulate the remote setpoint ratio
and/or the remote setpoint bias to prevent process bumps when the setpoint state is
switched to remote. Valid entries are:
BIAS MODE Field
This field specifies which remote setpoint bias value the FCM is presently using.
The configured entry is the initial bias mode. During runtime, this field changes
each time the mode is switched at the console. Valid entries are:
238
NO
do not change the output value
YES
change the output value
RATIO
FCM automatically manipulates ratio value of remote setpoint to
balance transitions to Remote
BIAS
controller automatically manipulates bias value of remote setpoint
to balance transitions to Remote
BOTH
the system can manipulate both bias and ratio
OFF
the balance feature is not used
REM
bias comes from the remote bias source
LOC
bias is from the local source (entered by operator at console)
OFF
controller does not use a bias signal
Appendix A Runtime Templates
3BUR002418-600 A