AI830
FILTER 01 through 08
Enter the lowpass filter time constant (in 10msec units) for each channel. Filter
times shorter than the update time are not usable. Update time can be calculated as:
The default value is 10 (100msec).
The possible range is:
10 to 65535.
LABEL
Enter a characteristic name to identify the AI830 Module of the station. The name
may contain up to 20 characters.
POSITION
Enter a number from 1 to 12 representing the position of the I/O module relative to
the FCI. The I/O module directly next to the FCI is number 1.
Default value is 1.
If positions are to be used for spare MTUs, the spares must be in place so the rest
of the I/O modules are numbered correctly. The spare MTU will use a position
number when it is on the ModuleBus.
POWER LINE FREQUENCY
Enter the power line frequency to filter out (notch) the signal.
The valid values are:
16, 50, and 60.
The default value is 60.
RANGE 01 through 08
The possible ranges are:
-80..80 C, -112..176 F
290
T
= 160ms + (n * 80ms)
Update
Therefore the T
Update
n = number of active channels 1...8
Range = 240ms to 800ms
Appendix A Runtime Templates
3BUR002418-600 A