Appendix A Runtime Templates
SETPT VALUE ON FAIL Field
This field specifies the setpoint value in effect upon a remote link failure. Valid
entry is a value in engineering units.
CHANGE SETPT ON FAIL Field
This field specifies whether a new setpoint value is supplied upon a remote link
failure. Valid entries are:
OUTPUT RETURN MODE Field
This field specifies the output mode to enter when the mode returns from Track.
Valid entries are:
OUTPUT MODE ON FAIL Field
This field specifies the output mode to enter upon a remote link failure. Valid entries
are:
OUTPUT VALUE ON FAIL Field
This field specifies the output value effective upon a remote link failure if the entry
in the CHANGE OUTPT ON FAIL field is YES. Valid entry is a value in percent.
3BUR002418-600 A
NO
do not change setpoint
YES
change setpoint
PREVIOUS go to the mode active before the output began tracking
MANUAL go to the Manual mode
AUTO
go to the Auto mode
PREVIOUS go to the mode active before the remote link failure
MANUAL go to the Manual mode
AUTO
go to the Auto mode
NO CHANGE remain in the present mode
PID Controller FCM
237