Continuous Moving Average Fcm - ABB 800xA Operation

For mod 300
Hide thumbs Also See for 800xA:
Table of Contents

Advertisement

Appendix A Runtime Templates
SAMPLE RATE Field
This field specifies the interval at which the FCM samples the input value. Valid
entry is in the form:
The SAMPLE RATE, PERIOD UNIT, and PERIOD SIZE fields must be configured
so the calculation is performed on no more than 127 samples.
PERIOD UNIT Field
This field specifies the time units for the period. It is used with the PERIOD SIZE
field to specify the period for the FCM. Section 10.4.7, Discussion, describes how
the period is used by periodic Extended Processing FCMs. Valid entries are:
PERIOD SIZE Field
This field specifies the size of the period. It is used with the PERIOD UNIT field to
specify the period of the FCM. Section 10.4.7, Discussion, describes how the period
is used by periodic Extended Processing FCMs. Valid entry is an integer from 1 to
99.
NUM OF INVALID SAMPLES Field
This field specifies the maximum number of samples with a BAD data quality that
can be present and still have output data quality GOOD. This field is not used when
the BAD INPUTS ACCEPTED? field is set to YES. Valid entry is an integer from 0
to 127.

Continuous Moving Average FCM

This module determines the moving average of an input over a specified number of
samples. The moving average is calculated in the standard mathematical fashion,
that is, when a new sample is added to the calculation, the oldest sample is
3BUR002418-600 A
NO
GOOD is the only acceptable data quality for the input
hh:mm:ss
the sample interval in hours, minutes, seconds
MONTHLY, LAST DAY, WEEKLY, DAILY, HOURLY, MINUTES
Continuous Moving Average FCM
281