Appendix A Runtime Templates
Default value is 1.
REPORT FAULTS 01 through 08
If channel faults are to be reported, enter a YES;
if not enter a NO.
The default value is YES.
RESERVED OPTIONS
This field reserved for future use. A zero (0) should be entered as a default value.
VALUE CYCLE TIME
Enter the channel value update period (msec) over the fieldbus. Refer to S800 I/O
User's Guide for details of AF 100 loading in relation to cycle time.
The valid values are:
1, 2, 4, 8, 16, 32, 64, 128, 256, 512, 1024, 2048 and 4096.
The default value is 128.

DI821

ACTIVE 01 through 08
If the channel is to be active enter a YES.
If the channel will not be used enter a NO.
The default value is YES.
AUTO DOWNLOAD
To automatically download the configuration to the I/O module enter a YES. In the
future, if the configuration is to be loaded locally enter a NO.
Default value is YES.
3BUR002418-600 A
DI821
307