Inverse Normalize Fcm; Scale Input Fcm - ABB 800xA Operation

For mod 300
Hide thumbs Also See for 800xA:
Table of Contents

Advertisement

Appendix A Runtime Templates
SCALING Field
This field specifies the scaling factor. Valid entry is any number.

Inverse Normalize FCM

The Inverse Normalize FCM converts a value from a normalized, dimensionless,
zero-based scale (percentage) to a value on an engineering units scale.
LOW RANGE Field
This field specifies the low range value for the input signal. Valid entry is any
number.
HIGH RANGE Field
This field specifies the top of range value for engineering units range of the result.
Valid entry is any number.
SCALING Field
This field specifies the scaling factor. Valid entry is any number.

Scale Input FCM

The Scale FCM converts a value from one engineering unit scale to its
corresponding value in another engineering unit scale.
OLD LOW RANGE Field
This field specifies low range value of the input. Valid entry is any number.
OLD HIGH RANGE Field
This field specifies high range value of the input. Valid entry is any number.
NEW LOW RANGE Field
This field specifies low range value of the result. Valid entry is any number.
3BUR002418-600 A
Inverse Normalize FCM
261

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents