ABB 800xA Operation page 285

For mod 300
Hide thumbs Also See for 800xA:
Table of Contents

Advertisement

Appendix A Runtime Templates
LABEL
Enter a characteristic name to identify the AI810 or AI890 Module of the station.
The name may contain up to 20 characters.
For the AI890 module, enter a description that includes the module type for
future reference to help alleviate confusion with an AI890 being used in the
AI810 templet.
LINEARIZATION 01 through 08
If the channel needs to apply the square-root-law linearization, enter a YES; if not
enter a NO.
The default is NO.
POSITION
Enter a number from 1 to 12 representing the position of the I/O module relative to
the FCI. The first I/O module directly next to the FCI is number 1.
Default value is 1.
If positions are to be used for spare MTUs, the spares must be in place so the rest
of the I/O modules are numbered correctly. The spare MTU will use a position
number when it is on the ModuleBus.
POWER LINE FREQUENCY
Enter the power line frequency to filter out (notch) the signal.
The valid values are:
16, 50, and 60.
The default value is 60.
RANGE 01 through 08
The valid values are:
0..10V (not valid for AI890)
0..20mA
3BUR002418-600 A
AI810, AI890
285