Linearization FCM
LO ENG UNITS Field (Low Engineering Units)
This field specifies the low limit of the engineering units range. Valid entry is any
number.
Linearization FCM
This FCM uses the table look-up method to linearize an input. The linearization
tables support thermocouples and RTDs (Resistance Temperature Devices) used by
the system. As an option, the FCM can linearize according to a table defined by you
via the Breakpoint Sets Templet. The result of this FCM is scaled in degrees C
(Celsius), F (Fahrenheit), K (Kelvin), or R (Rankine).
INVERSE AXIS? Field
This field specifies either normal or inverted axis. Valid entries are:
Normalize FCM
The Normalize FCM normalizes a signal from an engineering unit scale to a
dimensionless zero-based scale.
LOW RANGE Field
This field specifies the low range value for the input signal. Valid entry is any
number.
HIGH RANGE Field
This field specifies the top of range value for engineering units range of the result.
Valid entry is any number.
260
NO
do not invert axis (input value is the x value in the linearization
table, corresponding y value becomes the result)
YES
invert axis (input value is the y value in the linearization table,
corresponding x value becomes the result)