Time Related Calculator FCMs
LOCAL BIAS Field
This field specifies the local bias value. It is used when the bias mode is LOCAL.
Valid entry is any number.
LOCAL RATIO Field
This field specifies the local ratio value. It is used when the ratio mode is LOCAL.
Valid entry is any number.
Time Related Calculator FCMs
This section describes the active runtime fields on the following time related
calculator FCM templets. See
common fields.
•
•
•
•
•
•
•
•
•
•
Time Derivative FCM
The Time Derivative FCM performs a first order time differentiation on its input.
CONSTANT Field
This field specifies the value of the scaling constant. Valid entry is any number.
264
Time Derivative
Time Integration
First Order Filter
Totalizer
Lead/Lag Filter
Dead Time
Dead Time Compensation
Timer
Counter
Delay Timer
Common Calculator FCM Fields
Appendix A Runtime Templates
on page 256 for
3BUR002418-600 A