7.9 "Setting" Tab (Parameter Settings)
7.9.3 "Consumer" window
Table 7.19 "Consumer Tag" window settings (Continued)
Set the Producer Tag name of the communication destination.
Up to 100 one-byte alphanumeric characters can be used.
label)
Set the conditions for Class1 Tag communications. (
communication)
"Cyclic": Tag communications are performed at the RPI interval only. (Default)
"Application Trigger": Communications are performed at a specified timing even during communications at the
RPI interval.
Select the multiplier of the time-out value. (Default: x4)
The refresh device can be set with "Device" when the checkbox is selected.
When auto refresh settings are made in the "Refresh Parameter" window, the settings made here are disabled.
When using the auto refresh function, set the refresh target device and the start number of the device.
When "Refresh Device" is set in the "Refresh Parameter" window, settings for the refresh target device cannot
be made in this window. (
To set the refresh target device for each Tag in this window, delete the "Refresh Device" settings in the
"Refresh Parameter" window.
0 to 32752
Set the auto refresh target device.
0 to 61424
The settings can be made in the range of "Device" in "Q Parameter Setting" of GX Works2.
0 to 4212735
Note that other modules and EtherNet/IP modules having a different Nic No. must not use the
0 to 32767
same auto refresh target devices.
0 to EFF0
When using a bit device, make settings in 16-point units (such as M16).
0 to 4047FF
0 to 4184063
A reserved Tag can be configured when the checkbox is selected. (
A reserved Tag just reserves Data Area and does not communicate actually.
* 1 To use a tag name with 41 or more characters, the setting in "Add Own Nic" window is required.
(
Section 7.9.1 (1) Display and settings of the "Add Own Nic" window)
Description
*1
Section 4.2.1 (2) Timing of Class1 Tag
Section 7.9.7 "Refresh Parameter" window)
(Up to 32 alphanumeric characters when using a
Section 4.2.1 (4) Reserved tag)