7
UTILITY PACKAGE (SW1DNC-EIPUTL-E)
Item
Set the waiting time for a response to a request from the connected device when selecting "Originator Read" or
Timeout
"Originator Write" in "Setting Type".
Setting range: 30 to 10000 (Default: 30)
Set the conditions for Class3/UCMM Tag communications when selecting "Originator Read" or "Originator Write" in
"Setting Type".
Trigger
•"Cyclic": Tag communications are performed with the connected device periodically. This setting can be selected for
Class3 Tag communications only.
•"Application Trigger": Tag communications are performed at an arbitrary timing. (Default)
The refresh device can be set with "Device" when the checkbox is selected.
Refresh Device
When auto refresh settings are made in the "Refresh Parameter" window, the settings made here are disabled.
When using the auto refresh function, set the refresh target device and the start number of the device.
When "Refresh Device" is set in the "Refresh Parameter" window, settings for the refresh target device cannot be
Device
made in this window. (
To set the refresh target device for each Tag in this window, delete the "Refresh Device" settings in the "Refresh
Parameter" window.
L
0 to 32752
M
0 to 61424
D
0 to 4212735
R
0 to 32767
B
0 to EFF0
W
0 to 4047FF
ZR
0 to 4184063
A reserved Tag can be configured when the checkbox is selected. (
Reserved Tag
A reserved Tag just reserves Data Area and does not communicate actually.
7
- 47
7.9 "Setting" Tab (Parameter Settings)
7.9.4 "Message" window
Table 7.21 "Message Tag" window settings (Continued)
Section 7.9.7 "Refresh Parameter" window)
Set the auto refresh target device.
The settings can be made in the range of "Device" in "Q Parameter Setting" of GX Works2.
Note that other modules and EtherNet/IP modules having a different Nic No. must not use the same
auto refresh target devices.
When using a bit device, make settings in 16-point units (such as M16).
* 1 To use a tag name with 41 or more characters, the setting in "Add Own Nic" window is required.
(
Section 7.9.1 (1) Display and settings of the "Add Own Nic" window)
Description
Section 4.2.2 (4) Reserved tag)