TROUBLESHOOTING
Table 9.6 Communication error of the EtherNet/IP module (Continued)
Error code
Error
(Hex.)
C194
H
C195
H
C196
H
C197
H
C198
H
C199
H
C19A
H
Extended error
C19B
H
C19C
H
C19D
H
C19E
H
C19F
H
C1A0
H
Error detail
Tag communication is attempted to the target
specified by invalid Tag Parameter data.
The target device does not support the specified
connection type, connection priority, redundancy
owner, or size fixed/variable connection.
The connection size is invalid.
•The Target or router does not support the
specified connection size.
•The specified size does not match the size for a
fixed size connection.
•The requested size is too large for the specified
network.
The other end of the connection is not set.
The target device does not support the specified
RPI value.
Number of connections is exceeded.
The product code or vendor ID specified in the
electronic key logical segment does not match
the one of the target device.
Device type mismatch.
The device type specified in the electronic key
logic segment does not match that of the target
device.
Revision mismatch.
The major and minor revisions specified in the
electronic key logical segment do not match valid
revisions of the target device.
Invalid produced or consumed application path.
The produced or consumed application path
specified in Connection Path does not
correspond to a valid one in the target
application.
The configuration application path is invalid or
inconsistent.
The application path specified for the set data
does not correspond to a configuration
application.
Or, it is inconsistent with the consumed or
produced application path.
The connection request failed since there are no
non-listen only connection types currently open.
The maximum number of connections of the
target object has been exceeded.
•RPI is smaller than Production Inhibit Time.
•The Target
Originator RPI is smaller then the
Target
Originator Production Inhibit Time.
Action
Find the conditions for the target device to notify
this error and take measures.
(
the manual for the target device)
9.4 Error Code