Trigger condition (TRIGGERCONDITION)

Sets a trigger condition. Conditions can be created up to 32 and combined by "Trigger type" setting.
Condition type (TYPE)
Condition
Data condition
Comparison
Value change
Fixed cycle
System start
Trigger command
Event history
■Data condition
A trigger occurs when the specified data meets the specified condition.
• =: When the current value of monitored data is equal to the comparison value
• : When the current value of monitored data is not equal to the comparison value
• : When the current value of monitored data is greater than or equal to the comparison value
• >: When the current value of monitored data is greater than the comparison value
• : When the current value of monitored data is less than or equal to the comparison value
• <: When the current value of monitored data is less than the comparison value
• : When the monitored data turns FALSE  TRUE
• : When the monitored data turns TRUE  FALSE
• At change: When the current value of the monitored data changes
■Fixed Cycle
A trigger occurs in the specified interval after logging starts.
However, when the specified interval in the fixed cycle and the collection timing are not matched, a trigger occurs at the first
sampling after the specified fixed cycle interval is elapsed.
The cycle can be specified is 1 to 86400000 [ms].
• When the fixed cycle is specified to 10 seconds
Sampling interval
10 sec.
Fixed cycle (10 seconds)
■System start
A trigger occurs at system start (at completion of initialization processing) automatically. When this condition is used, set the
start condition of logging setting to "Starts automatically".
■Trigger command
A trigger occurs when System.LoggingRef[1..10].Cd.Trigger is set to TRUE.
15 LOGGING
466
15.1 Data Logging/Real-Time Monitor
Description
Data is compared with data or constant and a trigger occurs when a condition is satisfied. (>, , <, , =, )
A trigger occurs when a value is changed.
A trigger occurs every specified cycle (ms).
A trigger occurs at system start.
A trigger occurs when System.LoggingRef[1..10].Cd.Trigger is set to TRUE.
A trigger occurs when an event of the specified event history occurs.
A trigger occurs at the first sampling after
the specified interval is elapsed
10 sec.
Trigger occurrence
10 sec.