Container data center single-zone fire extinguishing system
Table of Contents

Advertisement

IDS1000 Container Data Center
User Manual
Figure 3-12 AUTO and MANUAL indicators on the gas extinguishing controller panel
If the status is manual, no solenoid valve driving signals will be generated from the controller when the
dual fire alarms from the smoke detector and heat detector are triggered.
Step 3 Simulate to trigger the smoke detector and heat detector.
When the gas extinguishing controller is tested and the first and second fire alarms are
triggered in sequence, the first loop indicator on the panel turns from off to blinking, and the
second loop indicator turns from off to steady on, which are normal reactions.
1.
Issue 01 (2014-3-15)
Use a conductor to short-circuit terminals 26 and GND to simulate to trigger the smoke
detector, as shown in
Figure
Figure 3-13 Short-circuiting terminals 26 and GND
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3-13.