Huawei IDS1000 User Manual page 29

Container data center single-zone fire extinguishing system
Table of Contents

Advertisement

IDS1000 Container Data Center
User Manual
2.
Issue 01 (2014-3-15)
After the short-circuiting, a smoke detector loop alarm is triggered, and the loop 1
indicator on the gas extinguishing controller panel blinks in red, as shown in
The controller reports a single loop alarm and the fire extinguishing alarm bell alarms.
Figure 3-14 Loop 1 indicator on the gas extinguishing controller panel
You can also use a smoke pistol to release smoke near the smoke detector until the detector is
triggered.
Do not clear the alarm. Proceed to the alarm simulation for the heat detector.
Use a conductor to short-circuit terminals 25 and GND to simulate to trigger the heat
detector, as shown in
Figure
Figure 3-15 Short-circuiting terminals 25 and GND
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3-15.
3 Power-On Commissioning
Figure
3-14.
23