Container data center single-zone fire extinguishing system
Table of Contents

Advertisement

IDS1000 Container Data Center
User Manual
Figure 3-19 Emergency startup/abort switch (panel not removed on the left, panel removed on the
right)
Press the startup button, the system enters the gas releasing delay mode, and the audible and
visual alarm begins to operate. After the countdown is complete, solenoid valve driving
signals are generated and the gas release indicator lights up. If you press the shutdown button
during the delay, the system will stop generating the solenoid valve driving signals.
Step 6 Test the functions of detectors.
Remove the smoke detector or heat detector from the base, as shown in
a network failure for the smoke detector or heat detector in this loop. The gas extinguishing
controller should report relevant loop faults, as shown in
detector or heat detector, and the fault is rectified.
Figure 3-20 Removing detectors
Issue 01 (2014-3-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Power-On Commissioning
Figure
3-20. Simulate
Figure
3-21. Reinstall the smoke