Huawei IDS1000 User Manual page 9

Container data center single-zone fire extinguishing system
Table of Contents

Advertisement

IDS1000 Container Data Center
User Manual
Compone
nt Name
Atomizer
nozzle
Gas release
indicator
Audible and
visual alarm
Emergency
start/abort
switch
Heat
detector
Smoke
detector
Alarm bell
System Features
Issue 01 (2014-3-15)
Appearance
All surface-mounted fire control cables are routed through metal hoses. The hose ends
are protected with grommets to prevent damage in case of a fire. Fire control cables are
routed and used separately which ensures secure and reliable power supplies to the fire
extinguishing system.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
1 Configuration Description
Function
Sprays an extinguishing agent to aisles in case
of a fire.
Displays "DON'T ENTER WHILE
RELEASING GAS" to warn onsite personnel
in case of a fire and the fire extinguishing
equipment releases the extinguishing agent into
the protected zone.
Generates dazzling flash signals and shrill
audible signals in case of a fire, reminding
onsite personnel to evacuate from the site
immediately, thereby avoiding major accident.
Starts or stops the gas extinguishing equipment
in case of a fire. The device is installed outside
the door of the protected zone. If you press the
glass plate to start extinguishing in emergency,
the red indicator lights up.
Evenly deployed in the aisles inside containers
to detect the temperature inside the containers
in real time. When it works in monitoring
mode, the red indicator blinks. When the
ambient temperature exceeds the alarm
threshold, it enters alarm mode and the red
indicator is steady on.
Evenly deployed in the aisles inside containers
to detect the smoke density inside the
containers in real time. When it works in
monitoring mode, the red indicator blinks.
When the onsite smoke density exceeds the
alarm threshold, it enters alarm mode and the
red indicator is steady on.
Produces clear and consistent sounds in case of
a fire, reminding onsite personnel to evacuate
from the site immediately, thereby avoiding
major accident.
3

Advertisement

Table of Contents
loading

Table of Contents