11.8

In-position Function

The "in-position function" turns on In-position signal (X16) while the accumulated pulse amount in the deviation
counter is within the specified in-position range (1 to 20479pulse) after deceleration started.
In-position signal (X16) can be used as the signal right before positioning completion.
(1) Control detail
In-position signal (X16) turns on when the accumulated pulse amount in the deviation counter becomes equal to
the value set in "
v
In-position signal
(X16)
Accumulated pulse amount is checked with the in-position range every 0.5ms.
(2) Precautions for control
(a) During speed control in the speed-position control switch mode
Accumulated pulse amount is not checked with the in-position range.
(b) Timing at which In-position signal (X16) turns off
In-position signal (X16) turns off at the following timings.
• When OPR starts
• When positioning control starts
• When two-phase trapezoidal positioning control starts
• When the speed-position control switch mode starts
• When JOG operation starts
In-position range" and stays on till the next start.
Pr.8
Pulse output
ON
OFF
Turns off at start.
CHAPTER 11 CONTROL SUB FUNCTIONS
Motor speed
Accumulated pulses
Turns on when the deviation counter value (pulse)
becomes the one within the set in-position range.
t
In-position setting
range
221
11