Entering limit values for safely limited speed (sls) into a sinamics s120 via profisafe with profinet
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

4 Configuration and project engineering
No.
Action
The following window is opened
after insertion. Here, please
select the subnet on which the
SINAMICS S120 is to be
operated.
In this example, this is the
"Ethernet 1" network.
16.
Also check the automatically
created
address. In the example, the
CU320-2 PN is assigned
address 192.168.0.2
Close the screen form using the
"OK" button.
Here, save and compile the
hardware configuration.
17.
Then please open "NetPro" to
insert the PG/PC into the
configuration.
From the catalog, select the
PG/PC object, and drag it to the
work area.
18.
Open it by double-clicking on the
properties window symbol.
Select the "Interfaces" tab, and
press the "New" button to
configure a network interface.
.
19.
An "Industrial Ethernet" interface
is required for the example.
Click "OK" to confirm the
selection.
30
Remark
PROFIsafe SLS Override
Version 1.0, Entry ID: 81682475