4 Configuration and project engineering
No.
Action
The OFF3 ramp-down time is
used for braking when SS1/SS2
is selected.
Set parameter
(p1135) to 0.5 seconds.
For this example, this means
that when SS1/SS2 is selected
19.
the drive operating at maximum
speed
(p1082) comes to a standstill in
0.5 seconds.
In this example, when an SLS
speed limit is exceeded, SS2
becomes active.
When using a Single
Line Module for 1AC 230V
(provided in the training
cases), now adapt
the DC link
parameters. To do this, open the
expert list and make the adjacent
parameter changes. Changes to
20.
the specified values can only be
made online.
Note:
As the SLM 5 kW has no
DRIVE-CLiQ interfaces,
it is not necessary to
parameterize the infeed.
Then save the configuration,
copy from RAM to ROM and
21.
load the configuration into the
PG/PC.
Now go offline again to continue
22.
the configuration.
40
p0210:
345V
p1248[0]:
240V
p1244[0]:
401V
See also FAQ ID: 27038754
Remark
PROFIsafe SLS Override
Version 1.0, Entry ID: 81682475