Siemens SINAMICS S120 Manual page 45

Entering limit values for safely limited speed (sls) into a sinamics s120 via profisafe with profinet
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

No.
Action
In screen form SS2, please also
change the value of the delay
time "Delay time SS2/STOP C -
> SOS active" to 500ms.
This stop response becomes
8.
active when the SLS limit is
exceeded.
Close the screen form using
"Close".
To be able to parameterize the
SLS safety function, please
press the "Safely limited speed
9.
(SLS)" button in the "Safety
Integrated" screen form.
For SLS level 1, please set the
value to 7500mm/min; in this
example this corresponds to a
speed of 750 rpm.
Please select "STOP C" as stop
response.
Now change the value of the
10.
delay time "Delay time between
sel. SLS -> SLS active" to
500ms.
Finally, set the selection for
"SLS limit via PROFIsafe" to
"Enable" and close the screen
form with "Close".
PROFIsafe SLS Override
Version 1.0, Entry ID: 81682475
4 Configuration and project engineering
Remark
45