Acceptance Test - Siemens SINAMICS S120 Manual

Entering limit values for safely limited speed (sls) into a sinamics s120 via profisafe with profinet
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

4 Configuration and project engineering
No.
Action
The safety program should then
8.
be generated and downloaded
into the CPU.
To do this, please press the
"Compile" button
followed by "Download".
In addition, the standard blocks
must be loaded to the F-CPU.
We recommend that blocks OB82 and OB86 are also integrated in order to
Note
tolerate the failure of the I/O (e.g. the drives for a power on reset) without the F-
CPU going into the STOP operating state.
4.8

Acceptance test

To verify safety-relevant parameter assignments/configurations, when the machine
is first commissioned, and also when safety-relevant parameters are changed, an
acceptance test must be performed. The acceptance test must be appropriately
documented. The acceptance reports must be appropriately stored and archived.
This involves specifications laid down in the machinery directive.
The acceptance test must be carried out after parameterization has been
completed and a power on reset.
You can find information about the acceptance test, the acceptance report and an
example of a corresponding acceptance report in the "Function Manual SINAMICS
S120 Safety Integrated" (FHS) /1/ in the Chapter Acceptance test and acceptance
report.
A script has been generated to simplify handling the acceptance test; this script is
available at no charge in the
SIEMENS Intranet) that can be downloaded by authorized personnel. This script
conveniently guides the user step by step through the acceptance test.
52
PRODIS entry 52248627
Remark
(link only available in the
PROFIsafe SLS Override
Version 1.0, Entry ID: 81682475