Mitsubishi Electric MELSEC iQ-R Series User Manual page 152

Serial communication module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Remote password check
If the remote password check has been set for C24, the C24 performs a remote password check when accessing to the
programmable controller from a target device using the C24 modem function.
The following is an overview of the CPU module remote password function.
Page 155 Applicability of remote password function
■Remote password function
The remote password function allows/prohibits access to the CPU module from a target device via the following modules.
• C24
• Ethernet module
• Built-in Ethernet port CPU
In the case of the Ethernet module, the remote password function can be used for data communications connections with a
target device. For details, refer to following manual.
MELSEC iQ-R Ethernet User's Manual (Application)
■Station to which the remote password and remote password check are set
• When a programmable controller system with one CPU module station
Parameter setting with Engineering tool
Remote password
Module subject to the remote
password check
• When a programmable controller system consisted of multiple CPU module stations
Set to the CPU module station (the CPU module on the host station in the figure below) which is the entrance of the
programmable controller system as viewed from the target device.
Set in the host station to allow/prohibit access to
the network system 1 from the target device.
(Host station)
Ethernet
RCPU
(Relay station)
module
Not set in the relay station or access station.
When set to a station other than the CPU module which is the entrance of the programmable controller system (relay station
or access station in the above figure), access to other stations beyond the set station is prohibited.
7 COMMUNICATIONS BY THE MODEM FUNCTION
150
7.1 Overview
RCPU
Remote
password
Remote
password
Ethernet
RCPU
module
Ethernet
Ethernet
RCPU
module
module
Network System 1
C24
Remote
Modem
password
check
Remote
password
check
Modem
C24
Ethernet
(Access station)
Ethernet
Target device
access source
Public line
Modem
Communication executing the
remote password check
Communication using MC protocol
Public line
Modem
Target device
access source