Mitsubishi Electric MELSEC iQ-R Series User Manual page 512

Serial communication module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Address
Purpose
Dec (Hex)
CH1
CH2
8210
8466
For designation
(2012H)
(2112H)
of transmission
control
8211
8467
(2013H)
(2113H)
8212
8468
(2014H)
(2114H)
8213 to
8469 to
Use prohibited
8215
8471
(2015H to
(2115H to
2017H)
2117H)
8216
8472
Send/receive
(2018H)
(2118H)
data monitoring
function
8217
8473
(2019H)
(2119H)
8218
8474
(201AH)
(211AH)
8219
8475
(201BH)
(211BH)
8220 to
8476 to
Use prohibited
8223
8479
(201CH
(211CH
to 201FH)
to 211FH)
8224 to
8480 to
For designation
8227
8483
of user frame
(2020H to
(2120H to
receiving
2023H)
2123H)
method
8228 to
8484 to
8231
8487
(2024H to
(2124H to
2027H)
2127H)
8232 to
8488 to
Use prohibited
8239
8495
(2028H to
(2128H to
202FH)
212FH)
8240 to
8496 to
For designation
8248
8504
of transparent
(2030H to
(2130H to
code
2038H)
2138H)
8249 to
8505 to
Use prohibited
8255
8511
(2039H to
(2139H to
203FH)
213FH)
APPENDICES APPENDIX
510
Appendix 3 Buffer Memory
Name
Transmission control start free space
designation
64 to 4095: transmission control start free
space
Transmission control end free space
designation
263 to 4096: transmission control end free
space
Nonprocedural no-reception monitoring time
method designation
0: Method 0 1: Method 1
System area
Send/receive data monitoring designation
0000H: No monitor/stop instruction
0001H: Monitor start instruction
0002H: Monitoring (set by C24.)
1002H: Monitoring stopped (set by C24.)
100FH: Monitor setting error (set by C24.)
Monitor option specification
0: OFF 1: ON
Stop at buffer full specification (b0)
0 timer error outbreak stop designation (b2)
For system (b1), (b3) to (b15)
Monitor buffer start address designation
(400H to 1AFDH, 2600H to 3FFDH)
Monitor buffer size designation
(0003H to 1A00H)
System area
User frame receiving method designation (1st
to 4th)
0: Method 0, 1: Method 1
Method 1 dedicated receive end data quantity
designation (1st to 4th)
0 or more: Method 1 dedicated receive end
data quantity designation
System area
Transparent code for sending specification (2nd
to 10th)
0000H: No specification
Other than 0000H: Specified (below)
• Transparent code (b0 to b7)
00H to FFH : Transparent code
• Additional code (b8 to b15)
01H to FFH : Additional code
System area
Defaul
Protocol
t value
MC
Non Bi
64
RW
263
0
RW
0
RW
0
CH1:
2600H
CH2:
3300H
0D00H
0
RW
0
0
RW
Reference
Pd
Page 237 C24 DTR
control contents and
free OS area
specification
Page 388 Send/
receive data
monitoring operation
Page 289 Setting of
receive user frames
Page 327
Registering
Transparent Codes
and Additional Codes