Mitsubishi Electric MELSEC iQ-R Series User Manual page 488

Serial communication module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error code
Error
(hexadecima
l)
7FCFH
System error
7FD1H
Modem function
error
7FD2H
Modem function
error
7FD3H
Modem function
error
7FD4H
Modem function
error
7FD5H
Modem function
error
7FD6H
Modern function
error
7FD7H
Modem function
error
7FD8H
System error
7FD9H
Modern function
error
7FDAH
Modem function
error
7FDBH
System error
7FDCH
Modern function
error
7FDDH
Modem function
error
27 TROUBLESHOOTING
486
27.4 Error Code List
Description
Signal
name
• The operating system of
C24 detected some error.
• The connection re-try
CHn
count designation is
ERR.
incorrect.
• The connection retry
CHn
interval designation is
ERR.
incorrect.
• The initialization/
CHn
connection timeout
ERR.
designation is incorrect.
• The number of
CHn
initialization retries
ERR.
designation is incorrect.
• The data No. for
CHn
initialization designation is
ERR.
incorrect.
• The data for connection of
CHn
the number specified in
ERR.
the data No. for
connection designation is
incorrect.
• The data for connection of
CHn
the number specified in
ERR.
the data No. for
connection designation is
incorrect.
• The operating system of
C24 detected some error.
• The line is connected to
CHn
the target, or the modem
ERR.
has not been initialized.
• The data No. for
CHn
connection designation is
ERR.
incorrect.
• The operating system of
C24 detected some error.
• The data for connection of
CHn
the number specified in
ERR.
the data No. for
connection designation is
incorrect.
• The connection timeout
CHn
error occurred.
ERR.
Corrective action
Page 490 Corrective actions
for system error
• Set the connection re-try
count to 1 to 5.
• Set the connection retry
interval to 90 to 300
(seconds).
• Set the time for the
initialization/connection
timeout to 1 to 60 (seconds).
• Set the number of initialization
retires to 1 to 5.
• Designate the registered
number of data for
initialization or '0'.
• Review the line type.
• Review the external line
outgoing number.
Page 490 Corrective actions
for system error
• Upon the completion of the
modem initialization, connect
the line to the target device
(via public line) while the line
has not been connected yet.
• Designate the registered
number of data for connection.
Page 490 Corrective actions
for system error
• Review the data for
connection.
• Review the telephone number
in the data for connection.
• Check whether the connection
target is connectable.
• Review the setting value for
the connection timeout.
• Review the data for
initialization.
Protocol
MC
Nonpr
Bidire
Prede
ocedu
ctiona
fined
ral
l

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents