Programmable controller CPU monitoring function setting
Set the system setting value to use the programmable controller CPU monitoring function.
Item
Programmable controller CPU monitoring function designation
Cycle time units designation
Cycle time designation (programmable controller CPU monitoring
interval time)
Send pointer designation
Output quantity designation
Block monitoring
Registered word block quantity designation
device
Registered bit block quantity designation
CPU error monitoring designation
n-th block
monitoring device
Description
Sets the timing to transmit the programmable controller
CPU monitoring results to a target device.
Sets the unit of the cycle time.
Set a cycle time.
(The unit depends on the cycle time units designation.)
Sets the pointer position of the user frame to be
transmitted.
Sets the number of user frame to be transmitted.
Sets the number of registered word blocks.
Sets the number of registered bit blocks.
Sets whether or not the monitoring for abnormality on
CPU module is performed.
Monitoring device
Sets the device code to be monitored.
*1
designation
Start device No.
Sets the start number of device to be monitored.
specification
Number of read
Sets the read point.
points specification
Monitoring condition
Sets the judgment conditions for the monitoring condition
specification
value.
(judgment condition
specification)
Setting range
• Do not use the function
• Fixed cycle send
• Condition match send
(Default: Do not use the
function)
• 100 ms
• Second
• Minute
(Default: Minute)
1 to 65535
(Default: 5)
0 to 100
(Default: 0: No designation)
0 to 100
(Default: 0: No designation)
0 to 10
(Default: 0: No designation)
0 to 10
(Default: 0: No designation)
• Do not monitor
• Monitor
(Default: Do not monitor)
Page 122 List of device
code
(Default: Do not designate)
Page 122 List of device
code
(Default: 0)
0000H to FFFFH
(Default: 0000H)
• Do not designate
• = (Edge)
• <>(Edge)
• <=(Unsigned, Edge)
• <(Unsigned, Edge)
• >=(Unsigned, Edge)
• >(Unsigned, Edge)
• <=(Signed, Edge)
• <(Signed, Edge)
• >=(Signed, Edge)
• >(Signed, Edge)
• =( Level)
• <>( Level)
• <=(Unsigned, Level)
• <(Unsigned, Level)
• >=(Unsigned, Level)
• >(Unsigned, Level)
• <=(Signed, Level)
• <(Signed, Level)
• >=(Signed, Level)
• >(Signed, Level)
(Default: Do not designate)
26 PARAMETER SETTING
26.2 Module Parameters
26
431