Hardware Information Communication Error "P/S" Occurs; Hardware Information Communication Error "C/N" Occurs - Mitsubishi Electric MELSEC iQ-R Series User Manual

Serial communication module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Hardware information communication error "P/S" occurs

Symptom
Hardware information
communication error signal
"P/S" turns ON.

Hardware information communication error "C/N" occurs

Symptom
Hardware information
communication error signal
"C/N" turns ON.
27 TROUBLESHOOTING
468
27.3 Troubleshooting by Symptom
Cause
Corrective action
The parity bit settings do not
match.
Sum check codes do not
match.
When CH1 and CH2 are set
for the interlink operation,
there is an interface to which
the cable is not connected.
■Remarks
If the cable is not connected to one of the interfaces when CH1
and CH2 are used for the interlink operation, the data may be
destroyed due to noise and may result in 'data cannot be
decoded' or 'cause of communications error'.
Cause
Corrective action
PC number is specified to the
self-station (FF), or a station
other than the station number
set with the network
parameter.
Routing parameters between
the CPU module with C24
mounted and the
communication destination
CPU module are not set.
Errors occurred on CC-Link IE
Controller Network or CC-Link
IE Field Network.
Errors occurred on the CPU
module of the host station on
CC-Link IE Controller
Network or CC-Link IE Field
Network.
Module installation address
designation for
communications with
Intelligent function module is
incorrect.
A command that cannot be
transmitted during RUN
(program, parameters, etc.)
was transmitted, or "Online
change" is set to be disabled.
• Review the data format between C24 and the target device,
and match the settings.
• Calculate to check if the sum check code transmitted from
the target device is correct, and correct the sum check code
if it's incorrect.
• When using CH1 and CH2 for the interlink operation,
connect the cable to both of the interfaces.
• When using CH1 and CH2 for the independent operation,
reconfigure the setting to the independent operation if it is
set to the interlink operation.
• Change the PC number to the self-station (FF) or the station
number set with the network parameter, and restart data
communications.
• Check the routing parameters and set them up to the
communication destination CPU module.
• Check the error contents by the status of SB and SW related
to CC-Link IE Controller Network and CC-Link IE Field
Network with the monitor function of Engineering tool etc.,
and take corrective actions in accordance with the reference
manuals for respective network.
• Change the transmission message designation data.
• Stop the CPU module and restart data communications.
• Enable the "Online change" by command and restart data
communications.
MC
Non
Bi
Pd
MC
Non
Bi
Pd