SIMATIC memory card
12.1 SIMATIC memory card – Overview
Deleting content from the SIMATIC Memory Card
You have the following options for deleting the content of the SIMATIC Memory Card:
● Delete files using Windows Explorer
● Format with STEP 7
Note
If you format the card with Windows tools, you will render the SIMATIC Memory Card
unusable as a storage medium for a CPU.
Deletion of files and folders is permitted, with the exception of the "__LOG__" and
"crdinfo.bin" system files. The CPU needs these system files. If you delete the files, you will
no longer be able to use the SIMATIC Memory Card with the CPU.
If you have deleted the "__LOG__" and "crdinfo.bin" system files, format the SIMATIC
Memory Card as described in the following section.
Formatting a SIMATIC Memory Card
Note
Formatting the SIMATIC Memory Card
Do not format the memory card with Windows tools. Formatting with Windows renders the
memory card initially unusable by a CPU.
You can find information on how to repair an inconsistent or incorrectly formatted card in the
following FAQ on the Internet
(https://support.industry.siemens.com/cs/ww/en/view/69063974).
To free up memory space on your SIMATIC Memory Card, you have the option of formatting
the SIMATIC Memory Card. During formatting, the entire contents of the memory card
including the project data of the SINAMICS Integrated are deleted.
The SIMATIC Memory Card may only be formatted in the CPU. Proceed as follows with the
SIMATIC Memory Card inserted:
Formatting with STEP 7:
● Establish an online connection.
● Open the online and diagnostics view of the CPU (either from the project context or via
"Accessible devices").
● In the dialog window, select "Functions > Format memory card" and then select the
"Format" button.
Results:
● The SIMATIC Memory Card is formatted.
● The CPU is temporarily unavailable.
● The project data on the CPU is deleted with the exception of the IP address.