Maintenance; Replacing System Components; Replacing A Defective Simatic Drive Controller - Siemens SIMATIC S7-1500 System Manual

Drive controller
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Maintenance

13.1

Replacing system components

13.1.1

Replacing a defective SIMATIC Drive Controller

Requirements
The power supply must be switched off before the SIMATIC Drive Controller is removed.
NOTICE
Material damage possible
Install or uninstalling the SIMATIC Drive Controller with the power connected can lead to
undefined states in your plant. Your automation system may be damaged as a result. Only
install/uninstall the SIMATIC Drive Controller if the power supply is disconnected.
Removing the SIMATIC Drive Controller
Proceed as follows to remove the SIMATIC Drive Controller:
1. Switch off the power supply.
2. Open the bottom front cover and remove the SIMATIC Memory Card from the slot.
3. Open the top front cover.
4. Loosen the terminal block for the 24 V power supply.
5. Release the DRIVE-CLiQ connectors to the SINAMICS S120 modules.
6. Release the connectors of the PROFINET interfaces or PROFIBUS interface.
7. Unplug the connectors to the digital inputs and digital outputs at interfaces X122, X132
and X142
8. Separate the connection to the protective conductor.
9. Loosen the fixing screws that are holding the SIMATIC Drive Controller to the cabinet
wall.
SIMATIC Drive Controller
System Manual, 11/2019, A5E46600094-AA
13
241

Advertisement

Table of Contents
loading

Table of Contents