Procedure: online via the SIMATIC Automation Tool
The procedure is described in the SIMATIC Automation Tool
(https://support.industry.siemens.com/cs/ww/en/view/98161300) user manual (included in
the SIMATIC Automation Tool).
Note
An update can only be performed for the CPU and not for the SINAMICS Integrated using
the SIMATIC Automation Tool.
Behavior after the firmware update
After the firmware update, check the firmware version of the CPU / SINAMICS Integrated.
You can find the firmware version for the CPU or SINAMICS Integrated under "Online &
diagnostics". In the working area, the firmware version is under "Diagnostics" > "General".
Additional information
For additional information on the topic of firmware update, refer to the STEP 7 online help
and the following FAQ on the Internet
(https://support.industry.siemens.com/cs/ww/en/view/109767138).
13.3

DRIVE-CLiQ component firmware update

DRIVE-CLiQ components
The SINAMICS Integrated (for SINAMICS S120 control units, the memory card) also
contains the firmware for the DRIVE-CLiQ components. With factory setting p7826 = 1, this
is automatically transferred from SINAMICS Integrated (for SINAMICS S120 control units
from the memory card) to the DRIVE-CLiQ components upon initial commissioning.
The firmware is saved to non-volatile memory in the DRIVE-CLiQ components in the event
of an upgrade.
Following a project download or automatic configuration, a firmware update is automatically
performed on all connected DRIVE-CLiQ components. This upgrades all DRIVE-CLiQ
components to the correct firmware versions.
SIMATIC Drive Controller
System Manual, 11/2019, A5E46600094-AA
13.3 DRIVE-CLiQ component firmware update
Maintenance
249