Procedure using the FUNCT button
You can save the service data to the SIMATIC Memory Card on the SIMATIC Drive
Controller with the FUNCT button. Before reading the data, make sure that there is sufficient
memory space on the SIMATIC Memory Card in the SIMATIC Drive Controller.
There are two basic methods for reading out service data:
● Reading out service data in the STOP or RUN state of the SIMATIC Drive Controller
● Reading out service data during SIMATIC Drive Controller startup
Reading service data in STOP or RUN allows you to back up the data quickly and easily on
a memory card. If backup is no longer possible (due to a persistent error, for example), you
can also back up the service data during startup immediately after switch-on.
Figure 14-1
Saving the service data in STOP or RUN state of the SIMATIC Drive Controller
1. To get to the function selection mode, press the FUNCT button for at least three seconds
and then release it. As an aid, the 7-segment display flashes "0".
After you release the button, you are in function selection mode. The 7-segment display
shows function "1" (Save service data).
2. To confirm the selection, press the FUNCT button within 10 seconds for at least 3
seconds and then release it. The service data is saved.
While the function is being executed:
– The 7-segment display shows "d" (DUMP)
– The ACT-LED flickers
– The RUN/STOP LED flashes yellow
– The ERROR and MAINT LEDs are off
After the function has been executed, the 7-segment display shows "0".
SIMATIC Drive Controller
System Manual, 11/2019, A5E46600094-AA
FUNCT button
SIMATIC Drive Controller FUNCT button
Test and service functions
14.2 Reading/saving service data
267