E8058 Drive System Not Ready For Operation - Bosch Rexroth IndraDrive Troubleshooting Manual

Hide thumbs Also See for Rexroth IndraDrive:
Table of Contents

Advertisement

8-12
Warning Diagnostic Messages (Exxxx)

E8058 Drive system not ready for operation

Cause
Error message of one or several drives of a drive
system
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Supported by Firmware Variant:
This fatal warning can occur for drive controllers in operation that are
interconnected via the module bus. If one of these drive controllers in
operation signals an error via the module bus, the drives that are to react
to signaled errors ("package reaction") react with shutdown. The reacting
drives display the warning E8058, the supply unit displays E2810 Drive
system not ready for operation.
The settings for error messages and error reactions for devices that are
interconnected via the DC bus and module bus are made in P-0-0118,
Power supply, configuration.
Remedy
Identify drive or drives signaling an error. Remove cause
of error at respective drive or drives
See also Functional Description "Power Supply"
E8058 - Attributes
Display:
E8058
Mess. no.:
E8058 (hex)
Rexroth IndraDrive
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
DOK-INDRV*-GEN-**VRS**-WA01-EN-P