Installation With Other Equipment - Fujitsu TeamPoS 2000 Installation And Maintenance Manual

Table of Contents

Advertisement

TeamPoS 2000
4.9

Installation with Other Equipment

In most cases, dedicated AC mains circuits are not required for the TeamPoS Series
terminals. In rare instances, other electrical equipment sharing power with the terminal
may cause adverse effects on the terminal. When this occurs, electrical isolation may be
required and is the responsibility of the customer or installing contractor.
Terminals at 115-volts
The following table details the electrical supply requirements for the TeamPoS Series
control unit with a nominal voltage supply of 115 volts.
Property
Earthing
Power System
Rated Voltage
Operational Voltage Limits
Rated Current
Rated Frequency
Operational Frequency Limits
Earth Leakage Current
Power Dissipation
Maximum HRC Fuse Rating for
External Short-circuit Protection
Main Power Cord: Length
Diameter:
Minimum Bend Radius:
4-4
Value or Description
The terminals are Class 1 equipment and must be supplied via a
socket-outlet which has a protective earthing contact connected to the
protective earth terminal of the installation.
The terminals are designed for use on a power system with an earthed
neutral, i.e., a TN or TT power system according to IEC 364. The
terminals must not be directly connected to a power system with an
impedance earthed neutral, i.e., an IT power system according to IEC 364.
115 Volts
100-120 VAC
4.6 A
60 Hz
57-63 Hz
< 1.0 mA
250 watts
20 A
3.00m (9.80 ft.)
8.0 mm (0.30 in.)
10.0 mm (0.40 in.)
Rev 3.0