Parameterization - Siemens Sinamics S120 Manual

Liquid-cooled chassis power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Line-side power components
3.4 Active Interface Modules, liquid-cooled
3.4.9.4

Parameterization

The thresholds for the temperature monitoring must be parameterized correctly for safe
operation:
● Alarm threshold p3667: 60 °C
● Trip threshold p3668: 70 °C
Note
Note regarding STARTER V4.4.1
The product is supported from STARTER version V4.4.1.
106
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7