Service for the cooling circuit
The following service is recommended for the cooling circuit:
● The coolant should be checked 3 months after the cooling circuit is filled for the first time
and, subsequently, once a year.
When analyzing the coolant, the concentration and the general conditions of the
inhibitor/antifreeze should be checked.
● If the cooling water becomes cloudy, is colored, or becomes contaminated by mold
spores, the cooling circuit must be cleaned and refilled.
● It is recommended that you contact the coolant manufacturer to analyze the liquid
coolant.
● If the coolant level has dropped, the loss should be corrected for closed or semi-open
circuits with a prepared mixture of coolant basis and antifreeze, see Chapters "Coolant
properties (Page 332)" and "Antifreeze, biocides, inhibitors (Page 335)".