Derating Factors As A Function Of The Ambient Temperature - Siemens Sinamics S120 Manual

Liquid-cooled chassis power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

5.3.6.2

Derating factors as a function of the ambient temperature

The units can supply 100 % output current at an ambient air temperature of between 0 °C
and 45 °C. The maximum output current decreases linearly to 90 % at ambient air
temperatures of between 45 °C and 50 °C.
Figure 5-26
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
Maximum current as a function of ambient temperature
Line Modules
5.3 Active Line Modules
195