Article number
DC link/motor connection
Max. conductor cross-sections
- DC link connection (DCP, DCN)
- Motor connection (U2, V2, W2)
- PE connection
Max. cable length
Degree of protection
Dimensions
- Width
- Height
- Depth
Frame size
Weight
Recommended fuse acc. to IEC
- Number per phase (connected in parallel)
- Rated current
- Frame size acc. to IEC 60269
Recommended fuse acc. to UL
Type 3NE3
- Number per phase (connected in parallel)
- Rated current
- Frame size acc. to IEC 60269
Type 3NB1/3NB2
- rated current
Rated power of a typical 6-pole standard induction motor based on I
1)
Rated power of a typical 6-pole standard induction motor based on I
2)
The specified power loss is the maximum value for a 100% utilization level. The value in normal operation is lower.
3)
This value applies to the water coolant option; for other coolant types, see Chapter "Cooling circuit and coolant proper-
4)
ties".
To achieve a UL-approved system, it is absolutely essential to use the fuse types specified in the table.
5)
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
6SL3325–
mm²
mm²
mm²
m
mm
mm
mm
kg
A
5)
A
A
1TE32-1AA3
1TE32–6AA3
Flat connection for M12 screw
Busbar
Busbar
2 x 95
2 x 95
2 x 95
2 x 95
300 (shielded) / 450 (unshielded)
IP00
IP00
150
150
746
746
545
545
FXL
FXL
41
41
3NE3230-0B
3NE3232-0B
1
1
315
400
1
1
3NE3230-0B
3NE3232-0B
1
1
315
400
1
1
3NB1231-
3NB1234-
4KK11
4KK11
315
400
or I
at 400 V 3AC 50 Hz.
L
H
or I
at 460 V 3AC 60Hz.
L
H
Motor Modules
6.6 Technical specifications
1TE33-1AA3
1TE35–0AA3
Busbar
Busbar
2 x 240
2 x 240
2 x 240
2 x 240
IP00
IP00
150
150
1172
1172
545
545
GXL
GXL
80
80
3NE3233
3NE3336
1
1
450
630
1
2
3NE3233
3NE3336
1
1
450
630
1
2
3NB1337-
3NB1345-
4KK11
4KK11
500
800