Article number
DC link/motor connection
Max. conductor cross-sections
- DC link connection (DCP, DCN)
- Motor connection (U2, V2, W2)
- PE connection
Max. cable length
Degree of protection
Dimensions
- Width
- Height
- Depth
Frame size
Weight
Recommended fuse acc. to IEC
- Number per phase (connected in parallel)
- Rated current
- Frame size acc. to IEC 60269
Recommended fuse acc. to UL
Type 3NE3
- Number per phase (connected in parallel)
- Rated current
- Frame size acc. to IEC 60269
Type 3NB1/3NB2
- rated current
Rated power of a typical 6-pole standard induction motor based on I
1)
Rated power of a typical 6-pole standard induction motor based on I
2)
The specified power loss is the maximum value at 100% utilization level. The value in normal operation is lower.
3)
This value applies to the water coolant option; for other coolant types, see Chapter "Cooling circuit and coolant proper-
4)
ties".
To achieve a UL-approved system, it is absolutely essential to use the fuse types specified in the table.
5)
When using fuses connected in parallel in each phase, if one fuse ruptures, then all of the fuses must be replaced.
6)
6.6.1

Overload capability

The Motor Modules have an overload reserve e.g. to handle breakaway torques.
In the case of drives with overload requirements, the appropriate base-load current must,
therefore, be used as a basis for the required load.
The criterion for overload is that the Motor Module is operated with its base load current
before and after the overload occurs (a load duration of 300 s is used as a basis here).
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
6SL3325–
mm²
mm²
mm²
m
mm
mm
mm
kg
A
5)
A
A
1TG38–1AA3
1TG41–0AA3
Flat connection for M12 screw
Busbar
Busbar
Busbar
Busbar
Busbar
Busbar
300 (shielded) / 450 (unshielded)
IP00
IP00
295
295
1516
1516
545
545
JXL
JXL
220
220
3NE3335
3NE3337-8
2
2
6)
6)
560
710
2
2
3NE3335
3NE3337-8
2
2
6)
6)
560
710
2
2
3NB2350-
3NB2357-
4KK16
4KK16
1000
1600
or I
at 500 or 690 V 3 AC 50 Hz.
L
H
or I
at 575 V 3 AC 60 Hz.
L
H
Motor Modules
6.6 Technical specifications
1TG41–3AA3
1TG41-6AA3
Busbar
Busbar
Busbar
Busbar
Busbar
Busbar
IP00
IP00
295
295
1516
1516
545
545
JXL
JXL
220
230
3NE3340-8
3NE3337-8
2
3
6)
6)
900
710
2
2
3NE3340-8
--
2
6)
900
2
3NB2364-
3NB2366-
4KK17
4KK17
2100
2400
233