Line-side power components
3.4 Active Interface Modules, liquid-cooled
Figure 3-29
Connection clip at the filter module
NOTICE
Damage to the device through not removing the connection clip with a non-grounded line
supply
Failure to remove the connection clip to the basic interference suppression module on a
non-grounded line supply (IT system) can cause significant damage to the device.
• With a non-grounded line supply (IT system), remove the connection clip to the basic
96
interference suppression module.
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7