Siemens Sinamics S120 Manual page 277

Liquid-cooled chassis power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

NOTICE
Damage to the dv/dt filter compact by using components that have not been released
When using components that have not been released, damage or malfunctions can occur
at the devices or the system itself.
• Only use a dv/dt filter compact that SIEMENS has approved for operation with
NOTICE
Damage to the dv/dt filter by exceeding the maximum output frequency
The maximum permissible output frequency when a dv/dt filter compact is used is 150 Hz.
The dv/dt filter compact can be damaged if the output frequency is exceeded.
• Operate the dv/dt filter compact with a maximum output frequency of 150 Hz.
NOTICE
Damage to the dv/dt filter compact during continuous operation with low output frequencies
Uninterrupted duty at an output frequency less than 10 Hz can result in thermal overload
and destroy the dv/dt filter.
• When using a dv/dt filter compact plus voltage peak limiter do not operate the drive
• You may operate the drive for a maximum load duration of 5 minutes at an output
NOTICE
Damage to the dv/dt filter compact by exceeding the maximum pulse frequency
The maximum permissible pulse frequency when a dv/dt filter compact is used is 2.5 kHz or
4 kHz. The dv/dt filter compact can be damaged if the pulse frequency is exceeded.
• When using the dv/dt filter compact, operate the Power Module or Motor Module with a
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
SINAMICS.
continuously with an output frequency less than 10 Hz.
frequency less than 10 Hz, provided that you then select operation with an output
frequency higher than 10 Hz for a period of 5 minutes.
maximum pulse frequency of 2.5 kHz or 4 kHz.
Motor-side power components
7.4 dv/dt filter compact plus Voltage Peak Limiter
277

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simanics s120

Table of Contents