Meaning Of The Led On The Voltage Sensing Module (Vsm) In The Active Interface; Module - Siemens Sinamics S120 Manual

Liquid-cooled chassis power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Line-side power components
3.4 Active Interface Modules, liquid-cooled
3.4.3.8

Meaning of the LED on the Voltage Sensing Module (VSM) in the Active Interface

Module

Table 3- 23
Description of the LED on the Voltage Sensing Module (VSM) in the Active Interface Module
LED
Color
RDY
---
Green
Orange
Red
Green/red Flashing
Green /
orange
or
red /
orange
78
Status
Description
Off
The electronics power supply is missing or lies outside the permissible tolerance
range.
Continu-
The component is ready for operation and cyclic DRIVE-CLiQ communication is
ous light
taking place.
Continu-
DRIVE-CLiQ communication is being established.
ous light
Continu-
This component has at least one fault.
ous light
Remark:
The LED is activated irrespective of whether the corresponding messages have been
reconfigured.
Firmware is being downloaded.
0.5 Hz
2 Hz
Firmware download is complete. Waiting for POWER ON.
flashing
light
2 Hz
Detection of the components via LED is activated (p0144).
flashing
Remark:
light
Both options depend on the LED status when module recognition is activated via
p0144 = 1.
Liquid-cooled chassis power units