2.5

Basic Line Filter for Active Line Modules with Active Interface Module

2.5
2.5.1

Description

Basic Line Filters are mainly effective in the frequency range from 150 kHz to 30 MHz; this
is the range relevant to ensure compliance with the appropriate standard.
Boundary conditions of Basic Line Filters for Active Line Modules with Active Interface
Module:
The Basic Line Filters can be used in accordance with the following general conditions for
ensuring CE conformity with regard to cable-borne interference:
● The machine/system must only be used in industrial networks.
● No. of axes ≤12.
● In conjunction with an Active Interface Module, they are designed for use in systems
● The Basic Line Filters are only suitable for connection to TN systems; otherwise an
2.5.2

Safety information

Line filters are only suitable for direct connection to TN systems.
Basic line filters may only be used in combination with the components listed in Chapter
"Combination options line reactors and line filters".
A ventilation clearance of 100 mm above and below the components must be observed.
This prevents thermal overloading of the filter.
The input and output connections/terminals must not be interchanged:
Incoming line cable to LINE L1, L2, L3 and
outgoing cable to line reactor at LOAD L1´, L2´, L3´
The line filter may be damaged if this is not observed.
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
2.5 Basic Line Filter for Active Line Modules with Active Interface Module
with a maximum total cable length of 350 m (shielded) in category C2 and 1000 m
(shielded) in category C3.
isolating transformer will be required.
CAUTION
WARNING
WARNING
WARNING
Line Connection Booksize
47