Siemens SINAMICS S120 Equipment Manual page 521

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Type
Power cable between line filter and line reactor
Power cable between line reactor and Line
Module
Power cable between
Motor and Motor Module to In = 9 A
Power cable between
Motor and Motor Module In = 18 A
Power cable between
Motor and Motor Module In ≥ 30 A
DRIVE-CLiQ signal cables MC500
DRIVE-CLiQ signal cables MC800
DRIVE-CLiQ signal cables FIX
Cable between the Braking Module and braking
resistor
1) To comply with EMC limit values, shielded cables (preferably Motion-Connect cables) must be used.
2) For greater lengths, suitable wiring must be connected by the user to provide overvoltage protection.
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
9.5 Information about electromagnetic compatibility (EMC) and cable routing
Cabinet Design and EMC Booksize
Maximum length [m]
10 (shielded/unshielded)
10 (shielded/unshielded)
50 (shielded)
75 (unshielded)
70 (shielded)
100 (unshielded)
100 (shielded)
150 (unshielded)
100
50
70
10
1)
1)
521