Cabinet Design and EMC Booksize
9.4 Arrangement of components and equipment
9.4.3

Drive line-up

Due to the current carrying capacity of the DC link busbars and their function, the
components must be arranged according to the following rule. From left to right:
● Line Module
● Motor Modules in order of power from the highest power to the lowest power
● DC link components (e.g. Braking Module, Control Supply Module, Capacitor Module)
512
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6